Service Engineers Inspection 60 Points CHECKLIST
Buying a used generator need not be a gamble.
We have years of experience in diesel generators. We are committed to providing only the highest quality used diesel generators, which is why all of the used generators we sell undergo a 60 point service inspection check and a full load test prior to dispatch.
With new stock arriving each week please contact us should you not be able to find the second-hand generator you are looking for. We also offer a wide range of new diesel generators from globally renowned brands such as Perkins, Cummins and Doosan.

How can we be confident that the diesel generator you purchase from GenPower Hub is the best quality second-hand generator that you can buy?
Below is a summary of some of the key areas we test and inspect:
Engine:
- Shutdowns tested at least 3 times during our test process.
- Physical connections to the base frame, radiator and alternator inspected.
- Charge alternator tested.
- Fuel pump inspected, fuel solenoid checked, fuel linkages lubricated.
- Fuel hoses inspected.
- Filters changed as required and air filter assembly checked.
- Oil tested and changed as required.
- Low oil pressure and engine temperature.
- Fan belts inspected, recorded and changed as necessary.
Radiator:
- All hoses checked.
- Fan blades and radiator fins checked.
- Radiator checked for fin blockage and cleaned as required.
- Coolant tested and changed as required.
- Fan guards checked and rectified.
- Radiator cap checked operationally.
Alternator:
- AVR checked and tested.
- Physical connections to the engine and base frame tested.
- Internal inspection of slip rings and diodes completed as required.
- Megger test if required.
Control Panel:
- Display checked.
- Warning lights and instrumentation checked.
- Fuses, relays and cables inspected.
- Panel settings for autostart and any timers recorded.
- Auxiliary inputs recorded.
Miscellaneous:
- Circuit breaker checked for correct operation.
- Batteries checked and changed as required.
- Battery charger and jacket water checked if applicable.
- Exhaust system checked.
- Exhaust condensate checked and drained.
Load Test:
- All generators tested at 25%, 50%, 75% & 100% of rated load.
- 50% load acceptance/load rejection tests completed and recorded.
- Voltage and Frequency variation on load recorded.
- Voltage and Frequency stability on load recorded.